Skip to main navigation Skip to search Skip to main content

Implementation of a Converter in Sequence Domain to Counter Voltage Imbalances

Research output: Contribution to journalArticlepeer-review

Abstract

This paper demonstrates the basic problem of the conventional d-axis and q-axis control applied to a voltage source converter (VSC) during a system imbalance. The specific imbalances studied are a balanced fault and an unbalanced fault at the terminals of the converter. The dc link voltage of the VSC is disturbed during the unbalanced fault due to negative sequence components in the system. The sequence characteristics of the system during an imbalance are further analyzed. A novel controller in the sequence domain is proposed. The positive sequence components of the control are implemented in the positive synchronous reference frame and the negative sequence components of the control are implemented in the negative synchronous reference frame. The negative sequence components are commanded to zero in the control. The approach demonstrates the stabilization of the voltage to a greater extent. The control also points out the need for a storage element when the VSC is to be used for application with that of a Doubly-Fed Induction Generators (DFIG) in wind turbines.

Keywords

  • Doubly-Fed Induction Generator
  • Unbalanced Fault
  • Wind power
  • Wind turbines

Disciplines

  • Electrical and Computer Engineering

Fingerprint

Dive into the research topics of 'Implementation of a Converter in Sequence Domain to Counter Voltage Imbalances'. Together they form a unique fingerprint.

Cite this