Abstract
Power transfer margins are studied with under load tap changing (ULTC) transformers based on both static and dynamic analysis. Static analysis results show that the ULTC can effectively increase the power transfer capability from a generation area to a load center by matching the generation side impedance with the load impedance. In dynamic analysis, both the ULTC and the load are considered as dynamic devices. The dynamic mechanism of mid-term voltage instability is analyzed using a load gain factor. Discrepancies in results from the two methods are explained. The effects of two types of ULTC--the network transformer and the distribution transformer are investigated. Both theoretical analysis and simulation results show that the network transformer is more beneficial for increasing the power transfer capability.